Flow Calculations
![]()
Notes on Flow Capacities Chart:
1. Design capacities calculated in accordance with BS 6367.
2. Distance between stop end and outlet should not exceed 50 x depth of gutter, and distance between outlets should not exceed 100 x depth of gutter.
3. Attention is drawn to paragraph 8.3.2 and Fig.3 of the above BS Code of Practice: i.e. careful placing of outlets enables smallest practicable gutter sizes to be used.
For the same total flow (Q), the gutter in Fig.A requires half the capacity of the gutter in Fig.B. Outlet capacities remain the same.

Similarly:
For the same total flow (Q), the gutter in Fig.C requires half the capacity of the gutter in Fig.D. Outlet capacities remain the same.
4. Where the length (Lg) of an eaves gutter is more than 50 times its overall depth (d) the following reduction factors should be applied.
Lg/d |
Reduction Factor |
|
50 |
1.0 |
|
100 |
0.93 |
|
150 |
0.86 |
|
200 |
0.80 |
Lg = either the distance between stop end and outlet. or half of the distance between two outlets.
5. Where a corner is near to an outlet a further reduction factor should be applied.
Less than 2m from outlet: reduction factor = 0.8
Between 2m and 4m from outlet: reduction factor = 0.9
6. Apparent anomalies can occur in the capacities chart as discharge characteristics change from 'weir' to 'orifice' type.
![]()
Calculations
Designs are based on rainfall rate of 75mm/hr.
Therefore RUN-OFF RATE (I/s) = EFFECTIVE AREA m² x 0.0208
Effective roof areas can be calculated as follows (from Building Regulations):
Type of Surface |
Design area (m²) |
|
Flat Roof |
Plan Area of Relevant Portion |
|
30° Pitch Roof |
Plan Area of Relevant Portion x 1.15 |
|
40° Pitch Roof |
Plan Area of Relevant Portion x 1.4 |
|
60° Pitch Roof |
Plan Area of Relevant Portion x 2 |
Simple Example
X = 5m, Y = 10m
Angle of roof = 30°

System required: Moulded Ogee with round pipe.
Design Area ('Effective Area') = 5 x 10 x 1.15 = 57.5m²
Run Off = 57.5m² x 0.0208 l/s per m² = 1.2 l/s
From the capacities chart, 100 x 75 gutter with 63Ø downpipe appears suitable, but check:
Lg / d = 10 / 0.075 = 133 ; therefore reduction factor = 0.86
Gutter capacity x reduction factor = 1.45 x 0.86 = 1.25 l/s, therefore the proposed system is suitable.
![]()
